The thermistor is one of the cheapest parts in a Hoshizaki KM cuber and one of the easiest to test. It also shows up in two of the three alarms on the control board. If your machine is beeping once or twice and stopping, it is worth ten minutes with a multimeter and a glass of ice water before you buy anything bigger.

The details below come from Hoshizaki's service manual for KM modular crescent cubers with the J-series control board. Other series work on the same idea, but use the manual for your model.

What the thermistor does

The thermistor is a temperature sensor mounted on the outside of the suction line coming off the evaporator. During harvest, the control board watches it to see the evaporator warm up as the hot gas frees the ice. When the thermistor reaches 48°F (9°C), the board reads about 3.9 kΩ from it and hands the end of the harvest over to the harvest timer.

So the board is trusting the thermistor to tell it when the ice should be coming off. If that reading is wrong, the harvest is wrong.

How a bad thermistor shows up

Hoshizaki lists the thermistor under two of the board's alarms (see our full alarm guide):

  • 1 beep, high evaporator temperature. The board saw the evaporator above 127°F. A shorted thermistor is on the list of causes, along with a stuck hot gas valve and hot water getting into the machine.
  • 2 beeps, harvest backup timer. Harvest ran past 20 minutes two cycles in a row. An open thermistor is the first thing Hoshizaki says to check, because the board never sees the temperature it is waiting for.

Neither alarm proves the thermistor is bad. Both are good reasons to test it first, since it is quick and it rules out a lot.

The ice water test

Turn the power off at the supply before you start.

  1. Remove the front panel and move the control switch to OFF.
  2. Remove the control box cover.
  3. Take the thermistor off the refrigerant tubing. It is fastened to the outside of the line, so this does not open the refrigeration system.
  4. Put the sensor end in a glass of ice and water and leave it for two to three minutes.
  5. Unplug the thermistor from the control board (the K3 connector on the J-series board) and measure the resistance across its two leads.

Hoshizaki's normal range in ice water is 4.7 to 6.2 kΩ.

  • Outside that range, or reading open or near zero: replace the thermistor.
  • Inside that range: the thermistor is fine. Put it back in its correct position on the line, plug it back into the board, replace the control box cover, set the switch to ICE, put the front panel back and turn the power on. Then keep working down the list for the alarm you had.

Putting it back correctly matters

A good thermistor mounted loosely, or in the wrong spot, will read the room instead of the suction line, and you will be right back where you started. Reinstall it exactly where it came off, following the component service section of your model's manual, and make sure it is held firmly against the tubing and covered the way it was before.

Ordering a replacement

Thermistors are model specific, so go by the part number in the parts list for your model and serial number rather than by appearance. Thermistors and other controls are in our controls section, and most part pages show which Hoshizaki models each part fits. If the alarm came back after you replaced the thermistor, or you are not sure which one you need, send us your model and serial number and we will help you narrow it down.